You probably do not come from: United Kingdom. If necessary, change to: United States
Service hotline 0208 213 2222
  1. Products
  2. Safety technology
  3. AS-Interface Safety at Work
  4. Operating elements
  5. AC010S

illuminated E-STOP with integrated AS-i connection

AC010S

E-stop illuminated IP67

illuminated E-STOP with integrated AS-i connection

AC010S

E-stop illuminated IP67

  • ce
  • ukca
  • asi
  • cul
Application
Application fool-proof E-STOP to EN ISO 13850
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 50
Integrated watchdog yes
Inputs
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply [V] 20
Input current Low [mA] < 4
Digital inputs protected against short circuits yes
Outputs
Electrical design AS-i
Max. current load per output [mA] 10
Short-circuit proof no
Actuator supply outputs AS-i
Operating conditions
Ambient temperature [°C] -25...60
Protection IP 67
Safety classification
Complies with the requirements
ISO 13849-1: 2015 category 4, PL e
IEC 61508 SIL 3
Mission time TM [h] 87600
AS-i classification
AS-i version 2.1
Extended addressing mode no
AS-i master profile M3; M4
AS-i profile S-7.B.E
AS-i I/O configuration [hex] 7
AS-i ID code [hex] B.E
AS-i certificate 74601
Mechanical data
Weight [g] 330.6
Dimensions [mm] 105 x 72 x 80
Materials PC-GF20
Displays / operating elements
Display
function LED, red
Electrical connection
Module connection M12
Remarks
Pack quantity 1 pcs.
Electrical connection
quick mounting technology for AS-i flat cable, IP 67:
Connector: M12; coding: A