You probably do not come from: United Kingdom. If necessary, change to: United States
Service hotline 0208 213 2222
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Compact field modules with screw mounting CompactLine
  5. AC2403

AS-Interface CompactLine module

AC2403

CompactM12 2 AI C V4A

AS-Interface CompactLine module

AC2403

CompactM12 2 AI C V4A

  • Easy to mount and wire
  • High shock and vibration resistance thanks to full potting
  • Clearly visible powerful LEDs for displaying operation, function and error
  • High protection rating for the requirements of harsh industrial environments
  • Robust M12 connectors for connecting sensors and actuators
  • ce
  • ukca
  • asi
  • cul
Application
Application field installation
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 250
Reverse polarity protection yes
Inputs / outputs
Number of inputs and outputs Number of analogue inputs: 2
Inputs
Max. total current rating of inputs [mA] 200
Number of analogue inputs 2; (Anschluss von 2- und 4-Draht-Sensoren)
Analogue input (current) [mA] 4...20
Operating conditions
Ambient temperature [°C] -25...80
Storage temperature [°C] -25...80
Max. relative air humidity [%] 90; (non condensing)
Max. height above sea level [m] 2000
Protection IP 67; (when flat cables are used E7400x / E7401x)
Tests / approvals
EMC
EN 61000-6-2
EN 62026-2
EN 50581
MTTF [years] 167
UL approval
power supply Class 2
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing IR addressing possible
Extended addressing mode no
AS-i master profile M3; M4
AS-i profile S-7.3.D
AS-i I/O configuration [hex] 7
AS-i ID code [hex] 3.D
AS-i certificate 99201
Mechanical data
Weight [g] 277
Type of mounting AS-i flat cables directly connectable
Materials PA; socket: stainless steel (316L/1.4404); threaded inserts in the lower part: stainless steel (316L/1.4404); screws in the lower part: stainless steel (316Cu/1.4578); piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
operation LED, green Voltage AS-i
errors LED, red
function LED, yellow channels AI1, AI2
Electrical connection
Module connection Flat cables
Accessories
Accessories (optional)
Protective cap: M12, E73004
Stainless steel sleeve, for installation in case of high mechanical stress , E70402
Remarks
Remarks
The module is exclusively supplied via the yellow AS-i cable.
When connecting a 2-wire or 3-wire sensor without own supply there has to be an external link between pin 3 and pin 4.
The inputs (pins 2 and 4) are electrically separated and have no connection to AS-i.
Pack quantity 1 pcs.
Electrical connection
Connector: M12; coding: A