You probably do not come from: United Kingdom. If necessary, change to: United States
Service hotline 0208 213 2222
  1. Products
  2. AC2630

I/O module for field applications

AC2630

FieldModuleDP 4x2DI M12

I/O module for field applications

AC2630

FieldModuleDP 4x2DI M12

  • Process data, configuration and diagnosis via PROFIBUS DP
  • Direct integration in the system
  • Robust design with full potting for use in harsh industrial environments
  • Easy set-up via GSD file
  • For direct connection of up to eight binary sensors to PROFIBUS DP
phase-out article
  • ce
Electrical data
Operating voltage [V] 20...29 DC
Current consumption [mA] < 85
Electrical separation no
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 8
Inputs
Number of digital inputs 8
Power supply [V] 20...29
Max. total current rating of inputs [mA] 500
Switching level high [V] 11...30
Switching level low [V] -3...5
Digital inputs protected against short circuits yes
Interfaces
PROFIBUS
Transmission rate 9,6...12000 kBit/s
Operating conditions
Ambient temperature [°C] 0...55
Storage temperature [°C] -25...85
Protection IP 67
Tests / approvals
EMC
EN 50081-2
EN 50082-2
Vibration resistance
IEC 68 parts 2-6 / IEC 68, parts 2-27
Mechanical data
Weight [g] 296.5
Materials housing: PA 6; potting compound: PU; contact pins: brass gold-plated
Remarks
Pack quantity 1 pcs.
Electrical connection - PROFIBUS
Connector: M12; coding: B
Electrical connection - Process connection
Connector: M12; coding: A
Electrical connection - power supply
Connector: M8; coding: A