You probably do not come from: United Kingdom. If necessary, change to: United States
Service hotline 0208 213 2222
  1. Products
  2. Industrial communication
  3. AS-Interface I/O modules
  4. Field modules for wet areas ProcessLine
  5. AC2910

AS-Interface ProcessLine module

AC2910

ProcessLine 8DI IP69K

AS-Interface ProcessLine module

AC2910

ProcessLine 8DI IP69K

  • Specially for the use in wet areas of the food and beverage industry
  • Hygienic design without corners and edges
  • Resistant to high-pressure cleaning with aggressive cleaning agents
  • Clearly visible powerful LEDs for displaying operation, switching status and error
  • ce
  • ukca
  • asi
  • cul
Application
Application hygienic and wet areas in the food industry
Electrical data
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 500
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 8
Inputs
Number of digital inputs 8; (2 x Slave)
Input circuit of digital inputs PNP; (type 2 according to IEC 61131-2)
Sensor supply of the inputs AS-i
Power supply [V] 18...30; (DC)
Max. total current rating of inputs [mA] 400
Input current High [mA] 6...10
Input current Low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Operating conditions
Ambient temperature [°C] -5...70
Max. relative air humidity [%] 90; (linearly decreasing to 50 % (40 °C) non condensing)
Max. height above sea level [m] 2000
Protection IP 68; IP 69K
Pollution degree 2
Tests / approvals
EMC
EN 62026-2
EN 61000-6-2
MTTF [years] 212
AS-i classification
AS-i version 2.1
Extended addressing mode yes
AS-i master profile M2; M3; M4
AS-i profile S-0.A.E
AS-i I/O configuration [hex] 0
AS-i ID code [hex] A.E
AS-i certificate 88901
Assignment of the data bits
data bit D0 D1 D2 D3
input 1 2 3 4
socket I-1/2 I-1/2 I-2 I-3/4 I-3/4 I-4
pin 4 2 4 4 2 4
Mechanical data
Weight [g] 644
Dimensions [mm] Ø 137.3 / L = 80
Materials threaded bush: stainless steel (316L/1.4404); LED-Fenster: PC; O-ring: EPDM; Protective cap: PP
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Electrical connection
Module connection M12
Accessories
Items supplied
Protective cap: M12, E70297
Accessories (optional)
Torque wrench:, E70390
Flat cable insulation displacement connector:, E70454
Remarks
Remarks
Inputs and outputs must be electrically isolated.
Do not connect any of the following points to an external potential:
I-, I+, I-1/2, I-2, I-3/4, I-4
The connections are electrically connected with the AS-i cable.
default setting of the ID1 codes: slave 1=1 / slave 2=2
The round cable connected to AS-i should not be longer than 2 m.
Pack quantity 1 pcs.
Electrical connection - AS-i
Connector: M12; coding: A; Tightening torque: 1.2...1.4 Nm
Electrical connection - Inputs
Connection Connector: M12; coding: A; Tightening torque: 1.2...1.4 Nm