You probably do not come from: United Kingdom. If necessary, change to: United States
Service hotline 0208 213 2222
  1. Products
  2. Sensors
  3. Flow sensors / flow meters
  4. Vortex flow meters with display
  5. SV7614

Vortex flow meter with display

SV7614

SVN34XXX50KG/US-100

Vortex flow meter with display

SV7614

SVN34XXX50KG/US-100

  • Reliable detection of flow and medium temperature
  • Precise linearized analogue output
  • Display can be rotated for optimum alignment
  • Clearly readable colour display with red/green colour change
  • Suitable for water, deionised water and cooling water
  • ce
  • ukca
  • cul
  • crn
Product characteristics
Number of inputs and outputs Number of analogue outputs: 2
Measuring range
80...1585 gph 1.3...26.4 gpm
Process connection threaded connection 3/4" NPT DN20
Application
Special feature Gold-plated contacts
Application for industrial applications
Media water; glycol solutions; coolants
Medium temperature [°F] 14...194
Pressure rating [bar] 12
Pressure rating [psi] 174
Note on pressure rating
up to 40 °C
MAWP (for applications according to CRN) [bar] 4.3
Electrical data
Operating voltage [V] 18...30 DC
Current consumption [mA] < 30
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] < 3
Inputs / outputs
Number of inputs and outputs Number of analogue outputs: 2
Outputs
Total number of outputs 2
Output signal analogue signal
Number of analogue outputs 2
Analogue current output [mA] 4...20
Max. load [Ω] 500
Short-circuit protection yes
Overload protection yes
Measuring/setting range
Measuring range
80...1585 gph 1.3...26.4 gpm
Display range
0...1900 gph 0...31.7 gpm
Resolution
5 gph 0.1 gpm
Analogue start point ASP
0...1270 gph 0...21.1 gpm
Analogue end point AEP
315...1585 gph 5.3...26.4 gpm
In steps of
5 gph 0.1 gpm
Measuring dynamics 1:20
Temperature monitoring
Measuring range [°F] 14...194
Display range [°F] -22...230
Resolution [°F] 1
Analogue start point [°F] 14...158
Analogue end point [°F] 50...194
In steps of [°F] 1
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range) ± 2 % MEW; (water)
Repeatability ± 0,5 % MEW
Temperature monitoring
Accuracy [K] ± 1
Response times
Flow monitoring
Response time [s] 1; (dAP = 0)
Damping process value dAP [s] 0...5
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 6
Software / programming
Parameter setting options Damping for the analogue output dAA; Display unit
Operating conditions
Ambient temperature [°F] 32...140
Note on ambient temperature
medium temperature < 176 °F
medium temperature < 194 °F: 32...122 °F
Storage temperature [°F] -4...176
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-27 5 g (11 ms)
Vibration resistance
DIN EN 60068-2-6 with water / 10...50 Hz 1 mm
with water / 50...2000 Hz 2 g
MTTF [years] 342
UL approval
UL Approval no. I002
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g] 514.5
Materials stainless steel (1.4404 / 316L); PC; PBT+PC-GF30; PPS; TPE-U
Materials (wetted parts) stainless steel (1.4404 / 316L); ETFE; PA 6T; PPS; FKM
Tightening torque [Nm] 30
Process connection threaded connection 3/4" NPT DN20
Remarks
Remarks
MW = measured value
MEW = Final value of the measuring range
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated
Diagrams and graphs
Pressure loss
dP Pressure loss
Q volumetric flow quantity
pressure rating (bar)